EKl1-63B Type B RCCB RCD
EKl1-63B Type B RCCB RCD
EKl1-63B Type B RCCB RCD

EKL1-63B Din Rail 10kA Type B RCCB RCD Residual Current breaker for Electric Vehicle EV Charging Pile

EKL1-63B Type B RCD has novel appearance design, compact structure, good reliability, and high safety. Type B RCDs can ensure maximum safety in many applications, such as EV Charging Station, Crane and Elevator, PV and Wind power plants, etc.

Inquire NOW PDF

EKL1-63B Din Rail 10kA Type B RCCB RCD Residual Current breaker for Electric Vehicle EV Charging Pile

Inquire NOW PDF

Porduct Overview

Description

EKL1-63B Type B RCD has novel appearance design, compact structure, good reliability, and high safety. The products comply with IEC61008-1, IEC62423 and other standards, and the product certification is complete; Hey ensure higher protection levels with maximum operational continuity under all working conditions. For this reason, Type B RCDs are considered universal devices because they provide protection against all the tripping waveforms listed in the Standards EN 62423.Type B RCDs can ensure maximum safety in many applications, such as EV Charging Station, Crane and Elevator and Wind power Plantses.

Technical parameters

Technical Data

RCCB Electrical Features
Mode Electromagnetic
Type (wave form of the earth leakage sensed) B
Rated current In 25,40,63A
Poles 2P(1P+N), 4P(3P+N)
Rated voltage Ue 2P 240V~,4P 415V~
Insulation voltage Ui 500V
Rated frequency 50/60Hz
Rated residual operation current(I△n) 30mA, 100mA, 300mA, 500mA
Rated residual making and breaking capacity (I△m) 500A(In≤40A), 10In (In>40A)
Short-circuit current Inc= I△c 10,000A
SCPD fuse
Break time under I△n ≤0.1s
Rated impulse withstands voltage (1.5/50) Uimp 4000V
Dielectric test voltage at ind.Freq. for 1min 2.5kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
RCCB Installation
Contact position indicator Yes
Protection degree IP20
Ambient temperature (with daily average≤35℃) -5℃~+40℃
Storage temperature -25℃~+70℃
Terminal connection type Cable/Pin-type busbar/U-type busbar
Terminal size top/bottom for cable 25mm2 18-3AWG
Terminal size top/bottom for busbar 25mm2 18-3AWG
Tightening torque 2.5Nm 22In-lbs
Mounting On DIN rail EN60715(35mm) by means of a fast clip device
Connection Power supply in both directions
Tripping Current Range
Lagging Angle I△n>0.01A I△n≤0.01A
0.35I△n≤I△≤1.4I△n 0.35I△n≤I△≤2I△n
90° 0.25I△n≤I△≤1.4I△n 0.25I△n≤I△≤2I△n
135° 0.11I△n≤I△≤1.4I△n 0.11I△n≤I△≤2I△n

Dimensions

Circuit Diagram

 

 

Installation size

 

Product selection form

Poles Rated Current (A) Sensitivity
30mA 100mA 300mA 500mA
1P+N 25A EKL1-63B-1N2530 EKL1-63B-1N25100 EKL1-63B-1N25300 EKL1-63B-1N25500
40A EKL1-63B-1N4030 EKL1-63B-1N40100 EKL1-63B-1N40300 EKL1-63B-1N40500
63A EKL1-63B-1N6330 EKL1-63B-1N63100 EKL1-63B-1N63300 EKL1-63B-1N63500
3P+N 25A EKL1-63B-3N2530 EKL1-63B-3N25100 EKL1-63B-3N25300 EKL1-63B-3N25500
40A EKL1-63B-3N4030 EKL1-63B-3N40100 EKL1-63B-3N40300 EKL1-63B-3N40500
63A EKL1-63B-3N6330 EKL1-63B-3N63100 EKL1-63B-3N63300 EKL1-63B-3N63500

Download Files

Porduct Overview

Description

EKL1-63B Type B RCD has novel appearance design, compact structure, good reliability, and high safety. The products comply with IEC61008-1, IEC62423 and other standards, and the product certification is complete; Hey ensure higher protection levels with maximum operational continuity under all working conditions. For this reason, Type B RCDs are considered universal devices because they provide protection against all the tripping waveforms listed in the Standards EN 62423.Type B RCDs can ensure maximum safety in many applications, such as EV Charging Station, Crane and Elevator and Wind power Plantses.

Technical parameters

Download Files

Get in Touch

Captcha Code
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All